Generator maintenance is the routine of checks, test runs and running-hours services that keeps a generating set ready to start and carry load. This is of utmost importance in case of standby generators, which might be idle for weeks and need to start operating within seconds. The oil, coolant, fuel, and batteries deteriorate irrespective of the operation of the generator.
Due to extreme temperatures in the UAE, the filter and fluid life is reduced, besides the batteries being highly affected, and the peak season when there could be a requirement for backup is summer. This manual explains the generator maintenance program on a weekly, monthly, and per operating hour basis, with special UAE modifications, and the support that GENAVCO provides to Green Power and GPS generators.
Weekly Checks
- Fluids: engine oil, cooling fluids, and fuel, with no leakage from any part of the unit.
- Battery: charging system functioning, battery terminals clean and tight, no bulge or corrosion.
- Controller: no current alarm on controller, set to automatic mode if it is a standby unit.
- Intake area and canopy: louvers and filters free from sand and other debris.
- Visual inspection: belts, hoses, and exhaust system without any looseness.
Monthly: Test Under Load
Running a generator without any load will tell you nothing. The test needs to involve starting the generator by its automatic transfer switch, taking a sizable portion of actual load, and running the unit until the required temperature is reached.
- The reasons for loading: Diesel engines that operate for extended periods at low load may result in the accumulation of unburned fuel and carbon deposits in the exhaust system, known as "wet stacking".
- Data to take: start time, voltage, frequency, oil pressure, coolant temperature, and alarm indications.
- Who should be involved in the testing process: facility personnel who know what to do in case something goes wrong during the testing process.
Service by Running Hours
| Service item | What it protects | When |
| Engine oil and oil filter | Bearings, pistons and liners | At the manufacturer's running-hours interval, or yearly on lightly used standby sets |
| Fuel filters and water separator | Injection system | With the oil service, sooner if fuel quality is poor |
| Air filter | Engine from dust | When the restriction indicator shows, more often in dusty sites |
| Coolant and belts | Cooling system and drives | Inspect at every service, replace on the manufacturer's schedule |
| Battery | Starting reliability | Test at every service, replace before the end of its rated life |
The engine maker's schedule sets the intervals. Our guide to the Perkins generator explains why well-documented engine platforms make service easier to plan, and the right engine oil grade matters as much as the interval.
Fuel Management of Standby Generators
- Diesel ages in storage: fuel that sits for months can degrade and collect water. Our guide to diesel generators covers fuel management in detail.
- Drain water: check and drain water separators and the tank sump.
- Maintain full tanks, but rotate them to keep fuel fresh; full tanks minimize condensation.
- Sample periodically: testing fuel from large standby tanks catches contamination before it blocks filters in an emergency.
GPS Generators From GENAVCO
1. GPS Industrial Range (10 kVA - 2,500 kVA)
- Confirmed specification: 10 kVA to 2,500 kVA with a closed canopy, hospital, residential and industrial silencer grades, 50 or 60 Hz supply, and compatibility with BMS and ATS.
- Confirmed support: GPS equipment supplied through GENAVCO is backed by installation and maintenance support.
Is your standby generator really ready?
Send us the generator make, rating, running hours and how it is used. We will propose a maintenance plan and service schedule.
Generator Maintenance in UAE Conditions
- Heating: radiators and cooling systems get the toughest tests during summers. It is important to clean the radiator fins and check the strength of the coolant before summer starts.
- Sand and Dust: Air filters and the canopy louvres get dirty fast. This matters even more for a silent generator, where acoustic panels and narrow air paths collect fine sand.
- Batteries: heat shortens battery life, so test batteries before summer.
- Coastal sites: salt air corrodes terminals and canopy fixings, so inspect them more often.
Maintenance Plan for Your Generator, In Steps
- Step 1 - List every generator with rating, engine, controller and running hours.
- Step 2 - Set weekly check sheets and a monthly loaded test for each standby set.
- Step 3 - Schedule services by running hours and by calendar for lightly used sets.
- Step 4 - Planning fuel tests and cleaning large standby fuel tanks.
- Step 5 - Stocking important spares such as filters, belts, and batteries for all the models.
- Step 6 - Reviewing the record every year based on the life span of the components.
The Importance of Maintaining Your Generator Properly
- Certified technicians and onsite vans: GENAVCO repairs and maintenance brings service to the site.
- Genuine parts: filters, belts and components that match the set.
- Generators and service from one supplier: Green Power generators and GPS sets supplied, installed and supported by GENAVCO.
- Part of the Juma Al Majid Group since 1967: an established UAE supplier with ISO 9001 certification.
Generator Maintenance Problems
- No-load testing: running without a load may mask problems that show up when there is a load.
- Service by time for standby generators: a generator that operates for 20 hours a year still requires annual service.
- Disregarding the battery: a discharged battery is one of the most frequent causes of failures in standby generators.
- Stale fuel: stale diesel clogs the filters at the most inopportune time.
- No documentation: without logs, it is impossible to know when the generator was last serviced.
Frequently Asked Questions
How often do generators require servicing?
Service based on the hours run as suggested by the engine manufacturer, and at least annually for standby sets which do not run often since oil, coolant, and fuel deteriorate over time.
How often should standby generators be tested?
Monthly testing under a load is usual practice.
What does generator maintenance entail?
Routine checking of fluids, battery and alarm, testing loaded operation once in a month, and servicing including oil, filters, coolant, belts, and batteries.
Does GENAVCO offer generator maintenance services in UAE?
Yes. GENAVCO offers repair and maintenance services with trained professionals and service vans at the site along with authentic parts for the generators that GENAVCO supplies.
Time to Plan Your Generator Maintenance?
Good generator maintenance is what turns a generator into reliable backup power. GENAVCO supports power generators in the UAE, from standby sets to portable generators, with service, parts and expertise.
Tell us what your generators are like and how they operate. We will then determine the appropriate maintenance schedule for you.